100 amp conductor size
[DOC File]SECTION I - OAS
https://info.5y1.org/100-amp-conductor-size_1_98e283.html
100 amp sockets can be used for 125 amp services. c) 200 amps meter sockets are slightly larger than the 100 amp size. They normally come with a blank plate on top and you must order “hubs” in the pipe size you need. 200 amp meter sockets can be used for all size services up to 125 amp.
[DOCX File]SPECIFICATIONS
https://info.5y1.org/100-amp-conductor-size_1_cfe3f4.html
Conductor Material: Copper. Minimum Conductor Size: No. 12 AWG. CONNECTORS AND SPLICES. ULlisted, factoryfabricated wiring connectors of size, ampacity rating, material, type, and class for application and service indicated. Comply with Project's installation requirements and as specified in Part 3 "Wire and Insulation Applications" Article.
[DOC File]Seattle
https://info.5y1.org/100-amp-conductor-size_1_4af8d5.html
Stock No. AMP. Cat. No. Conductor. Size Desired Min. Stocking . Requirements/Unit Manufacturers. Units/Package Unit. Price/EA 580671 602142 336.4 10 8 $22.95 580672 602143 397.5 100 8 $23.15 580673 602248 477 0 1 $24.78 580676 602237 954 30 1 $49.46 All items are to be AMP …
[DOC File]Seattle
https://info.5y1.org/100-amp-conductor-size_1_718d0e.html
Stock No. AMP. Cat. No. Conductor. Size Desired Min. Stocking . Requirements/Unit Manufacturers. Units/Package Unit. Price/EA 580671 602142 336.4 10 8 $24.26 580672 602143 397.5 100 8 $24.47 580673 602248 477 0 1 $26.19 580676 602237 954 30 1 $52.28 All items are to be AMP …
[DOCX File]Transatlantic Division, U.S. Army Corps of Engineers
https://info.5y1.org/100-amp-conductor-size_1_d42524.html
100 kW/ (380 volt x 1.73) = 152 amps. 152 amps x 125% (NEC 219.A.1) = 190 amps. The nearest breaker size would be 200 amps. You would need to size the wire based on the 200 amps. The 200 amp breaker is rated at 75 degrees and is in a panel rated at 75 degrees. The conductor is rated at 90 degrees.
[DOC File]BASIC NEC CODE RULES AND DESIGN PRACTICE
https://info.5y1.org/100-amp-conductor-size_1_7ba407.html
Minimum size service that should be installed is 100 A, 20 circuit for very small buildings, comfort stations 200 A or 225 Amp, 40 circuit 120/240V, 1 phase for all others. This may be too small for actual load, must do load calculations.