Product Description: NEMA MG1, three phase, four pole, re-connectable brushless synchronous generator with brushless exciter. Each Generator will be rated: 2 x 500 KW - 1000kW, 1,250 kVA, at 0.8 power factor, 480Y/277 volts, 60 Hz at 1800 rpm, for a total of 2000 KW, single 2000KW’s and Single 1000KW are not permitted, each 1000 KW must ...
ELECTRIC POWER SYSTEM SPECIFICATION
Hard-wiring a contact from each generator providing status of generator on-line and generator common alarm ensure supervisory monitoring through any situation. The control system shall provide pre-wired customer use I/O: 4 relay outputs (user definable functions), 4 contact inputs, 2 analog inputs, communications support via RS232, and RS485.
[DOCX File]Ray Township, Michigan
https://info.5y1.org/25kw-3-phase-generac-generator_1_2a93d5.html
May 21, 2019 · Grader supported by Lascoe to approve bid as presented from Budget Electric Generators for the installation of a Generac Generator, 22KW air cooled, including parts and labor , 7 year extended warranty and 5 maintenance visits, one per year, and removal of old 20 KW generator.
[DOCX File]biznet.ct.gov
https://info.5y1.org/25kw-3-phase-generac-generator_1_cea086.html
Town of Waterford Board of Selectmen Invitation to Bid. Preventive. Maintenance . and . Service . for. Town-Wide Generators. Bid #18-1. 21. The Purchasing Agent will accept sealed
[DOC File]SAP - College of Charleston
https://info.5y1.org/25kw-3-phase-generac-generator_1_194da7.html
Item # Qty / UOM Generator Location Manufacturer Model # Output Unit Price Total 1 2 EA Berkeley Campus ONAN 15 C-4XR12382AC. 277/280, 1800RPM, 3-phase, 60 Hz, S/N F810573270 15 KW 2 2 EA Main Campus, Bldg 100 ONAN 12.5 JC18R/17164AB. 240/460, 1800 RPM, 3-phase, 60 . Hz, s/n F850764722 12.5 KW
[DOC File]SECTION 263213 - ENGINE GENERATORS
https://info.5y1.org/25kw-3-phase-generac-generator_1_262826.html
Sustained Short-Circuit Current: For a 3-phase, bolted short circuit at system output terminals, system shall supply a minimum of 250 % of rated full-load current for not less than ten (10) seconds and then clear the fault automatically, without damage to generator system components.
[DOC File]Home | SC.GOV
https://info.5y1.org/25kw-3-phase-generac-generator_1_cdb8a9.html
Phase/Wire/P.F. 3 Phase/4 Wire . Volts 277/480 . Amps 15 . Building Name: Commission for the Blind Building (3 Generators) 1430 Confederate Ave. Columbia, SC. Location #1-outside, behind Building B #2-outside, behind Building C . Year Installed 1975 1975 2003 . Make/Mfg. Katolight Corp. Katolight Corp. Katolight Corp. Type 13681 15241-1
[DOC File]GENERATOR - Henry Davis
https://info.5y1.org/25kw-3-phase-generac-generator_1_7acdaa.html
1. Before making adjustments run the generator about 15 minutes under a light load to reach normal temperatures. 2. Engine speed determines the output voltage and current frequency of the generator. 3. Increasing the speed increases the voltage and frequency and vice versa. 4. An accurate voltmeter should be connected to the generator output.
[DOC File]Weekly Generator Test Log - GTAA
https://info.5y1.org/25kw-3-phase-generac-generator_1_6b8e54.html
Weekly Generator Test Log. Building Address: Generator Size: Kw. Voltage Amperage HZ. Frequency Coolant. Temperature Coolant Level Oil Pressure Oil Level Fuel Level Main Tank Fuel Level Dry Tank Hours @ Start Hours @ Stop Room Temperature AB AC …
SolarEdge Technologies, Inc.
We currently offer our second generation of inverters which come in two models: a one-phase inverter designed to address the residential market (2.2 kilowatts (“kW”) to 11.4 kW) and a three-phase inverter designed to address the residential market in certain European countries and the commercial market (4 kW to 33.3 …