The installing contractor shall install General Purpose Transformer per the manufacturer's recommended installation, operation, and maintenance manual and comply with all applicable codes. Make sure that the transformer is in upright and leveled position.
[DOC File]PRODUCT SPECIFICATION FOR A 15 TO 75 KVA,
https://info.5y1.org/75-kva-transformer-installation_1_d9eb17.html
The isolation transformer shall be mounted on rubber isolation pads to prevent 60 Hz hum of the core from being transmitted to the frame. The transformer core clamp shall be grounded to the frame through a 1" copper strap. The Transformer insulation system shall be 220° C. The transformer temperature rise shall be 150° C rise.
[DOC File]SECTION 16275 - Government of New York
https://info.5y1.org/75-kva-transformer-installation_1_ba2637.html
Jul 08, 2009 · Transformer Rating Recommended Minimum Distance from Building 75 kVA or less 10 ft. 76-333 kVA 20 ft. More than 333 kVA 30 ft. b. FM Loss Prevention Data 5-4/14-8 Tables 2A and 2B: Table 2A Factory Mutual Required Separation Distance Between Outdoor Liquid Insulated Transformers and Building. HORIZONTAL DISTANCE
[DOCX File]SECTION 16460 DRY-TYPE TRANSFORMERS
https://info.5y1.org/75-kva-transformer-installation_1_7702d5.html
Minimum Linear Load Efficiency: NEMA TP-1 and EPA ENERGY STAR compliant; 97.5 percent for 30 kVA, 97.7 percent for 45kVA, 98.0 percent for 75 kVA, 98.2 percent for 112.5kVA, 98.3 percent for 150 kVA, 98.5 percent for 225 kVA, 98.6 percent for 300 kVA, 98.7 percent for 500 kVA.
[DOCX File]Electrical Equipment | Electrical Solutions – G&W Electric
https://info.5y1.org/75-kva-transformer-installation_1_d87d16.html
• External 1.0 KVA oil transformer for 120 VAC supply power with hardware to mount on standard aluminum frame • External 0.75 KVA solid dielectric transformer for 120 VAC supply power with hardware to mount on standard aluminum frame ... • Orientation mounting bracket for left, centered or right installation. 2.8 LABELING. A. Hazard ...
SECTION 262213- LOW-VOLTAGE DISTRIBUTION …
Mounting: Transformers 75 kVA and less shall be suitable for wall, floor, or trapeze mounting. Transformers larger than 75 KVA shall be suitable for floor or trapeze mounting. Coil Conductors: Continuous copper windings with terminations brazed or welded. The winding shall be epoxy encapsulated providing rigid construction and quieter operation.