Grounded wye transformer connections
[DOC File]Section 3 - Baylor ECS
https://info.5y1.org/grounded-wye-transformer-connections_1_f3e764.html
Therefore, the zero sequence impedance of a transformer depends on the winding connections. In the case where one side of a transformer is connected grounded-wye, and the other side is delta, circulating zero sequence currents can be induced in the delta winding. In that case, the zero sequence impedance "looking into" the transformer is ...
[DOC File]INTRODUCTION - Power Partners USA
https://info.5y1.org/grounded-wye-transformer-connections_1_d7d60b.html
grounded-wye transformers These transformers have one end of the winding brought out through insulated H.V. bushings and the other end connected internally to the tank. A substantial and thoroughly reliable ground connection should be made between the tank and a low resistance ground through a conductor of adequate cross section.
The Ungrounded Wye - Delta Transformer Connection
A method of accurately modeling three-phase transformer connections for power-flow and short-circuit studies has been demonstrated using the ungrounded wye-delta connection.
[DOC File]1 - Cooper Industries
https://info.5y1.org/grounded-wye-transformer-connections_1_d4f67f.html
Grounded Wye - Wye. For Grounded Wye - Wye configurations the high voltage neutral shall be internally tied to the low voltage neutral and brought out as the Ho. X. o. bushing. [ ] Wye - Grounded Wye. For Wye - Grounded Wye configurations the high voltage neutral shall be brought out as the Ho. bushing on the primary side and the low voltage ...
[DOC File]SECTION 16276 - Government of New York
https://info.5y1.org/grounded-wye-transformer-connections_1_e01d5a.html
a. Connect 3 phase transformer primaries in delta. Do not use wye primaries except in special cases because of “problem connections”. When wye primaries are used, special consideration must be given to the grounding connections and the type of core/coil construction to prevent tank overheating, voltage and load balance problems. 4.
[DOC File]ANSI 3 PHASE - PADMOUNTED TRANSFORMERS - MTR
https://info.5y1.org/grounded-wye-transformer-connections_1_1a6960.html
4.1.13 Five—legged core/coil assembly suitable for grounded WYE—grounded WYE connections, DELTA-ground WYE connections or DELTA—DELTA connections as required. 4.1.14 Handhole cover bolted onto tank top (protected by weather cover). 4.1.15 Tap changer handle for de—energized operation only. 4.1.16 Drain valve with sampling device.