Heavy wall steel pipe sizes

    • [DOC File]SECTION 210529 - HANGERS AND SUPPORTS FOR FIRE SUPPRESSION ...

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_2737c9.html

      Floor Support for Hot Pipe Sizes 6 Inches (152.4 mm) and Over: Adjustable cast iron roll and stand, steel screws, and concrete pier or steel support. Shied for Insulated Piping 2 Inches and Smaller: 18-gauge (1.31 mm) galvanized steel shield over insulation in 180 degree segments, at least 12 inches (300 mm) long at pipe support.


    • PIPE AND PIPE FITTING SCHEDULE

      Underground building drain pipe and fittings to be Cast Iron Soil Pipe ASTM A74, service weight, hub and spigot soil pipe and fittings. Pipe and Fittings shall have a heavy coating of coal tar varnish or ashpaltum on both inside and outside surfaces. Hubs to have Neoprene Compression Gaskets: ASTM C564.


    • [DOC File]APPENDIX B—RECOMMENDATIONS FOR DESIGN AND CONSTRUCTION OF

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_839e82.html

      If large particle sizes are used, differential aeration corrosion (pitting) may occur at locations where the large particles or debris contact the steel tank bottom. In this case, cathodic protection may not be effective in preventing pitting. B.2.7 Consider the chemistry of native soil and fill material when designing the foundation.


    • [DOC File]SECTION 055000 - METAL FABRICATIONS

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_ce604f.html

      Steel Sections: ASTM A992, hot-dip galvanized for exterior use. Steel Pipe: ASTM A53, Type S, Grade B, Schedule 40 typical unless otherwise noted. Pipe used for handrails and railings shall be [hot-dip galvanized after fabrication][powder coated] for exterior use, [1-1/2 inch][32mm] ID, unless otherwise noted.


    • PIPING SPECIALTIES FOR STEAM UTILITY DISTRIBUTION

      Fabricate the body and slip of ASTM A53, Grade B, seamless steel pipe, Schedule 40 for steam service and Schedule 80 for condensate service. Provide the joint with stainless steel limit stops designed for full line pressure thrust at 3.0 times or greater design pressure.


    • [DOC File]Sec. 2.3: Steel Water Pipe

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_d73181.html

      ANSI/AWWA C200 Steel Water Pipe—6 In. (150 mm) and Larger. ANSI/AWWA C205 Cement-Mortar Protective Lining and Coating for Steel Water Pipe – 4 In. (100 mm) and Larger- Shop Applied. ANSI/AWWA C206 Field Welding of Steel Water Pipe. ANSI/AWWA C207 Steel Pipe Flanges for Waterworks Service—Sizes 4 In. Through 144 In. (100 mm through 3,600 mm)


    • [DOC File]STANDARDS PUBLICATION NO

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_5b0ea8.html

      Steel straps sized for copper tubing may be copper-plated or copper-coded for identification purposes in addition to Section 8.2. 8.4 UNDERWRITERS LABORATORIES MARKING Those parts which are UL-listed shall be marked in accordance with the requirements of any applicable UL Standards, i.e., UL5B, Standard for Strut-Type Channel Raceways & Fittings.



    • [DOC File]SECTION 232000 - HVAC PIPING

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_d034d5.html

      BLACK STEEL PIPE, SCHEDULE 80. Pipe: Schedule 80, in accordance with ASTM A120 or A53. Fittings: Extra heavy Class 300 screwed cast iron on 2 inches and below, extra strong welding fittings in accordance with ASTM A234 for 2 1/2 inches and above. Service: Pumped and gravity steam condensate return. COPPER PIPE


    • [DOC File]SECTION 334100 - STORM UTILITY DRAINAGE PIPING

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_293d4b.html

      Resilient Pipe Connectors: ASTM C 923, cast or fitted into manhole walls, for each pipe connection. Neoprene rubber shall meet ASTM C 443 and have a minimum thickness of 3/8 inch. Pipe clamps shall be of corrosion-resistant steel. Pipe connectors shall be one of the following:


    • [DOCX File]11 65 00

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_9bcf9c.html

      Construct posts of 3½"-o.d. heavy wall pipe, and provide each set with a tie off post and a winch post. Each post has a cast aluminum top pulley cap with a 1¾" diameter aluminum pulley. Tensioning ratchet shall be a cold rolled steel assembly with a removable handle for safety and a spring-loaded safety latch.


    • [DOCX File]SECTION 055000 - METAL FABRICATIONS

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_621187.html

      Fabricate sleeves for bollard anchorage from steel pipe with 1/4-inch- thick steel plate welded to bottom of sleeve. Make sleeves not less than 8 inches deep and 3/4 inch larger than OD of bollard. Fabricate internal sleeves for removable bollards from Schedule 80 steel pipe or 1/4-inch wall-thickness steel tubing with an OD approximately 1/16 ...


    • [DOC File]SECTION 211100 - FIRE SUPPRESSION PIPING

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_cdcc1d.html

      Below grade, dry stand pipe. LIGHT WALL BLACK STEEL PIPE. Pipe: ASTM A135 or A53. For Fire Protection: Schedule 10 in sizes up to 5 inches. 0.134-inch wall thickness for 6-inch. 0.188-inch wall thickness for 8-inch and 10-inch. For chilled water and heating water piping 8 inches and over:


    • [DOCX File]SECTION 08 11 13 - HOLLOW METAL DOORS AND FRAMES

      https://info.5y1.org/heavy-wall-steel-pipe-sizes_1_b53311.html

      Steel pipe spacers 6 mm (1/4 inch) inside diameter, welded to plate reinforcing at jamb stops, or hat shaped formed strap spacers 50 mm (2 inches) wide, welded to jamb near stop. Drill jamb stop and strap spacers for 6 mm (1/4 inch) flat head bolts to pass through frame and spacers.