Honeywell three way valves
[DOCX File]23 0901
https://info.5y1.org/honeywell-three-way-valves_1_83be2a.html
Size three (3) way mixing or diverting valves not directly associated with pump sub-circuit for 3 psi to 5 psi pressure drop. Sub-circuit is defined as branch supply and return piping to terminal device, including valve, coil, control valve, and balancing valve.
[DOCX File]SECTION 23 09 01
https://info.5y1.org/honeywell-three-way-valves_1_beb884.html
Two way valves shall have equal percentage characteristics, three way valves linear characteristics. Pressure Independent Hydronic Control Valves (where scheduled on drawings): ... Carbon dioxide sensor shall be Honeywell model C7242A or equivalent. TEMPERATURE SENSORS: RTDs AND TRANSMITTERS. Room Thermostats: Temperature sensor shall have as ...
Honeywell Building Controls Commercial HVAC Solutions
2-Way and 3-Way VBN Control Ball valves 1/2 to 3 inches (2 ½ inches for 3-way): Valves shall be available with female national pipe thread pipe (fNPT) fittings. Minimum Requirements: The control ball shall have an equal percentage flow characteristic provided by a …
[DOCX File]FireWarden-50 Engineering Spec (DOC) - NOTIFIER by …
https://info.5y1.org/honeywell-three-way-valves_1_d5ea1f.html
2.PIV (post indicator valve) or main gate valves shall be equipped with a supervisory switch. 3.The switch shall be mounted so as not to interfere with the normal operation of the valve and adjusted to operate within two revolutions toward the closed position of the valve control, or when the stem has moved no more than one-fifth of the ...
[DOCX File]15973b
https://info.5y1.org/honeywell-three-way-valves_1_91c900.html
Use three-way valves sized for a maximum pressure drop of 5 psi and that have linear characteristics so that the valve pressure drop remains constant regardless of the valve position. ... Johnson Controls VG7000 Series, Belimo G200 and G300 Series, and Honeywell V5011/V5013 Series. Minimum size for globe valves shall be 0.7 Cv. Globe valves 2-1 ...
[DOC File]Niagara Div 23 09 Guide Specification - Honeywell
https://info.5y1.org/honeywell-three-way-valves_1_60966f.html
Control Valves: Control valves shall be 2-way or 3-way pattern as shown and constructed for tight shutoff at the pump shut-off head or steam relief valve pressure. Control valves shall operate satisfactorily against system pressures and differentials. Two-position valves shall be ‘line’ size.
Nearby & related entries: