Johnson controls steam globe valve
[DOCX File]Section 23 22 13 - STEAM AND CONDENSATE HEATING PIPING
https://info.5y1.org/johnson-controls-steam-globe-valve_1_b00726.html
1)High pressure steam 413 kPa (60 psig) and above nominal MPS system): Cast steel body, ASTM A216 grade WCB, 1034 kPa (150 psig) at 260 degrees C (500 degrees F), 111/2 to 13 percent chrome stainless steel solid disc and seats. Provide 25 mm (1 inch) factory installed bypass with globe valve on valves 100 mm (4 inches) and larger.
[DOCX File]23 0901
https://info.5y1.org/johnson-controls-steam-globe-valve_1_83be2a.html
Valve body shall be 150 psi psi bronze globe type with threaded connections for two (2) inches and smaller and Class 150 steel with flanged connections for two and one half (2-1/2) inches and larger. Actuators shall be diaphragm type with remote liquid filled bulb with six (6) feet of armored tubing, unless otherwise indicated.
[DOC File]SECTION 232215 - STEAM AND CONDENSATE SPECIALTIES
https://info.5y1.org/johnson-controls-steam-globe-valve_1_261565.html
steam pressure reducing valve installation Provide globe valve bypass, gate valves, strainers, reducers, traps, safety valves, and pressure gauges for a complete pressure reducing station. Valves, strainers, etc. shall be line size with concentric pipe reducers at the pressure reducing valve.
[DOCX File]SECTION 23 09 01
https://info.5y1.org/johnson-controls-steam-globe-valve_1_beb884.html
Accuracy shall be +/- 0.25% full scale with a compensated temperature range of 30 to 150 deg F and a maximum working pressure of 250 psig. Install transmitter in a pre-manufactured bypass valve assembly with shut-off valves, vent valves and a bypass valve, all enclosed in a NEMA 1 enclosure.
[DOC File]Brown University
https://info.5y1.org/johnson-controls-steam-globe-valve_1_44045b.html
Valve and damper schedules with all control parameters listed. ... Steam and HTHW valves shall be Normally-Closed. VALVE AND DAMPER ACTUATORS: Actuators on all steam and High Temperature Hot Water (HTHW) control valves shall be electric with a manual-override feature. ... Johnson Controls temperature sensors shall be 1000 Ohm PLATINUM.
[DOCX File]Steam and Steam Condensate Specialties
https://info.5y1.org/johnson-controls-steam-globe-valve_1_262895.html
Pressure gauges for interior steam systems shall be 4-1/2 inches with back connection when used on a panel; otherwise they shall have bottom connections. Each gauge shall be provided with Ashcroft carbon steel needle valve and a siphon rated for the steam pressure and temperature.
[DOCX File]Home | Infrastructure Planning and Facilities
https://info.5y1.org/johnson-controls-steam-globe-valve_1_4cdb04.html
Fluid control valves shall be single seated, straight through, globe with renewable hardened seats and high lift contoured stainless steel plugs and seats, allowing tight shutoff. Valves shall have modified linear control characteristic for steam valve service, and equal percentage characteristic for water service.