    • [DOC File]LARGE PUMP OR ENCLOSURE SOUND INSULATION KIT

      https://info.5y1.org/vibration-absorbing-pad_1_4dfc1f.html

      4 x Sound Absorbing Mat (32mm thick with a black film face on one side 1200 x 900mm) 2 x Anti-Vibration Pad (20mm thick high density rubber panel 1m x 1m) 2 x Can Sta-Put aerosol adhesive. 1 x Acoustic Sealant. 1 x Set Installation Instructions. Please read through these instructions before commencing work to familiarise yourself with


    • [DOCX File]SECTION 01000 - GENERAL REQUIREMENTS

      https://info.5y1.org/vibration-absorbing-pad_1_66c965.html

      Balance pumps per ANSI / Hydraulic Institute procedures. Perform electronic vibration analysis for all pumps 1/2 hp and above. Unless noted otherwise, the maximum allowable RMS (filter in) velocity at maximum pump motor speed, measured at each pump and motor bearing, shall not exceed 0.13 inches/sec in the vertical, horizontal and axial directions.


    • [DOCX File]Home | Infrastructure Planning and Facilities

      https://info.5y1.org/vibration-absorbing-pad_1_674e7e.html

      SECTION 230548 - VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT. GENERAL. RELATED DOCUMENTS. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.


    • [DOCX File]Documents & Reports - All Documents | The World Bank

      https://info.5y1.org/vibration-absorbing-pad_1_7aa4e6.html

      Noise and vibration pollution control measures (noise barriers, use of sound-absorbing materials, use of low noise equipment and carts, and rubber floating slab track, vibration damping track with rubber pad etc.) have been identified in all critical sensitive points along the line.


    • [DOC File]Section 23 05 41 - NOISE AND VIBRATION CONTROL FOR HVAC ...

      https://info.5y1.org/vibration-absorbing-pad_1_6a0035.html

      1.1 DESCRIPTION. Noise criteria, vibration tolerance and vibration isolation for HVAC and plumbing work. 1.2 RELATED WORK. A. Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION: General mechanical requirements and items, which are common to more than one section of Division 23.


    • [DOCX File]Section 23 05 41 - NOISE AND VIBRATION CONTROL FOR HVAC ...

      https://info.5y1.org/vibration-absorbing-pad_1_0a23eb.html

      D.Allowable Vibration Tolerances for Rotating, Non-reciprocating Equipment: Not to exceed a self-excited vibration maximum velocity of 5 mm per second (0.20 inch per second) RMS, filter in, when measured with a vibration meter on bearing caps of machine in vertical, horizontal and axial directions or measured at equipment mounting feet if bearings are concealed.


    • [DOCX File]SECTION 16460 DRY-TYPE TRANSFORMERS

      https://info.5y1.org/vibration-absorbing-pad_1_e0e431.html

      The core and coil shall be completely isolated from the enclosure by means of vibration absorbing mounts. ... For floor and trapeze transformer installations, use one pad type Korfund Elasto-Grip, waffle at each corner of the transformer, sized for load of 50 pounds per square inch.


    • [DOCX File]Section 23 05 41 - NOISE AND VIBRATION CONTROL FOR HVAC ...

      https://info.5y1.org/vibration-absorbing-pad_1_b710c2.html

      SECTION 23 05 41NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT. 1.1 DESCRIPTION. ... room test condition prior to occupancy and design condition after occupancy which may include the addition of sound absorbing material, such as, furniture. ... 6.Seismic Pad (Type DS): Pads shall be natural rubber / neoprene waffle with steel top ...


    • [DOC File]Flo Fab

      https://info.5y1.org/vibration-absorbing-pad_1_0027d0.html

      The vibration isolation pad shall be adequately sized to provide room for the pump, pump trim, and piping supports. The pad shall be constructed base shall be fabricated of 6” channel steel fully enclosed at sides and ends, with securely welded cross members and fully open grouting area (for field grouting).


    • [DOC File]2

      https://info.5y1.org/vibration-absorbing-pad_1_e0bb07.html

      Support units during shipment on non-staining shock absorbing material. ... Choice of bearing pad can usually be left to fabricator; coordinate selection with structural engineer if required. ... Place self-consolidating concrete without vibration in accordance with PCI Interim Guidelines for the Use of Self-Consolidating Concrete.


    • [DOCX File]SECTION 210548 - VIBRATION AND SEISMIC CONTROLS FOR FIRE ...

      https://info.5y1.org/vibration-absorbing-pad_1_b3105c.html

      Vibration Mountings & Controls, Inc. Pads: Arranged in single or multiple layers of sufficient stiffness for uniform loading over pad area, molded with a nonslip pattern and galvanized-steel baseplates, and factory cut to sizes that match requirements of supported equipment.


    • [DOC File]SECTION 15241 - MECHANICAL VIBRATION CONTROLS AND SEISMIC ...

      https://info.5y1.org/vibration-absorbing-pad_1_916179.html

      Seismic Pad (Type DS): Pads shall be felt, cork neoprene waffle, neoprene and cork sandwich, neoprene and fiberglass, neoprene and steel waffle, or reinforced duck and neoprene, with steel top plate and drilled for an anchor bolt. ... Resilient Components: 19 mm thick, replaceable, shock-absorbing neoprene insert. VIBRATION ISOLATION BASES ...



    • [DOC File]Section 23 05 41 - NOISE AND VIBRATION CONTROL FOR HVAC ...

      https://info.5y1.org/vibration-absorbing-pad_1_ba4f8d.html

      D. Section 23 31 00, HVAC DUCTS AND CASINGS: requirements for flexible duct connectors, sound attenuators and sound absorbing duct lining. ... A. Bolt pad mounted equipment, without vibration isolators, to the floor or other support using ASTM A307 standard bolting material. B. Floor mounted equipment, with vibration Isolators: Type SS. Where ...


    • [DOCX File]SECTION 26 22 00 - DOA Home

      https://info.5y1.org/vibration-absorbing-pad_1_17013f.html

      Isolate core and coil from enclosure using vibration absorbing mounts. ... All transformers mounted to floor shall be installed on a 3-1/2” concrete pad. Use flexible conduit, 2 ft. (0.6 m) minimum length, for connections to transformer case. ... [Mount transformers on vibration isolating pads installed between the floor and the transformer ...


    • [DOCX File]Section 23 05 51 - NOISE AND VIBRATION CONTROL FOR BOILER ...

      https://info.5y1.org/vibration-absorbing-pad_1_65f536.html

      Bolt pad mounted equipment, without vibration isolators, to the floor or other support using ASTM A307 standard bolting material. Floor mounted equipment, with vibration isolators, Type SS. Where Type N isolators are used provide channel frame base horizontal restraints bolted to the floor, or other support, on all sides of the equipment.