Water cooled condenser
[DOCX File]Section 23 64 00 - PACKAGED WATER CHILLERS
https://info.5y1.org/water-cooled-condenser_1_2b92a9.html
b.Condenser water temperature. c.Entering and leaving chilled water temperature and control set points. d.Automatic lead-lag switch. 3.Safety Functions: Following conditions shall shut down the chiller and require manual reset to start: a.Loss of chilled water flow. b.Loss of condenser water flow (for water-cooled chillers only).
[DOC File]PART 1 - browardschools
https://info.5y1.org/water-cooled-condenser_1_f1599d.html
Factory assembled and tested packaged water cooled liquid centrifugal and/or screw chiller furnished complete with compressors, compressor motors, condenser, evaporator, interconnecting refrigerant piping, refrigeration accessories, motor starters, microprocessor module control panel including gauges with indicating lights and auxiliary ...
[DOC File]Specification – Smardt water Cooled Chillers
https://info.5y1.org/water-cooled-condenser_1_fbcf36.html
C. The evaporator, condenser, and expansion valve shall be configured to operate as one refrigerant circuit. The chiller unit compressors shall be designed for mechanical and electrical isolation to facilitate service and removal. 2.3 DESIGN REQUIREMENTS. A. Provide a complete water-cooled, TurboCor compressor equipped chiller as specified.
SECTION 236427 - AIR-COOLED WATER CHILLERS
The entire chiller package shall have factory mounted VFD. When VFD s cooled by condenser water, piping to and from the VFD shall be factory installed. The variable speed drive must include a harmonic filter that meets IEEE Standard 519-1992. The IEEE Std 519-1992 Filter Includes:
[DOC File]Guide Specification Smardt water Cooled Chillers
https://info.5y1.org/water-cooled-condenser_1_56ce82.html
Chiller shall be able to vary the condenser water temperature to the minimum condition independently of condenser water flow rate and chilled water flow rate. H Each compressor shall be electrically and mechanically isolated so that if a compressor fails or needs service it can be serviced or removed from the chiller without disabling the other ...
[DOCX File]NAPPS SWU Water Cooled Condensing Unit - Napps Tech
https://info.5y1.org/water-cooled-condenser_1_25fff2.html
The Water Cooled Condensing Unit shall have a capacity of _____ tons when operating at ____ °F saturated suction temperature and supplied with ____ gpm of ____ °F condenser water. Water pressure drop shall not exceed ____ psi through the condenser. Unit full load cooling EER at these conditions shall be no less than _____. Condenser
[DOC File]Guide Specification Smardt water Cooled Chillers
https://info.5y1.org/water-cooled-condenser_1_0c9a42.html
D. Air-Cooled Condenser: 1. Air cooled packaged chillers and controls shall be capable of reliable operation between 32°F and 105° ambient air temperature. 2. Air-cooled condensers coils shall utilize epoxy coated aluminum fins which shall meet ASTM B117 1000hr salt spray test.