[DOCX File]SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM …
https://info.5y1.org/fused-disconnect-switch-sizes_1_c90376.html
Disconnect switch electrical interlock where indicated. Motor starters shall be a minimum NEMA Size 1. Fused disconnect switch units, circuit breaker units, and combination motor starter units shall have the disconnect and the door interlocked to prevent the unit door from being opened when the unit is on.
[DOC File]Section 26 29 21 - DISCONNECT SWITCHES
https://info.5y1.org/fused-disconnect-switch-sizes_1_2d9996.html
A. Install disconnect switches in accordance with the NEC and as shown on the drawings. B. Fusible disconnect switches shall be furnished complete with fuses. 3.2 SPARE PARTS . Two weeks prior to the final inspection, furnish one complete set of spare fuses for each fusible disconnect switch …
[DOCX File]Section 26 29 21, Enclosed Switches and Circuit Breakers
https://info.5y1.org/fused-disconnect-switch-sizes_1_5ab58d.html
A.This section specifies the furnishing, installation, and connection of fused and unfused disconnect switches (indicated as switches in this section), and separately-enclosed circuit breakers for use in electrical systems rated 600 V and below. 1.2 RELATED WORK
[DOC File]PSG Section 26 28 16.13 - Eaton
https://info.5y1.org/fused-disconnect-switch-sizes_1_b52be5.html
The Contractor shall furnish and install the low-voltage fused and non-fused switches as specified herein and as shown on the contract drawings. Related Sections. References. The switches and all components shall be designed, manufactured and tested in accordance with the latest applicable standards: NEMA KS-1. UL 98. Submittals – for Review ...
[DOCX File]ELECTRICAL FOR STEAM UTILITY DISTRIBUTION
https://info.5y1.org/fused-disconnect-switch-sizes_1_5b1aca.html
Provide combination, full voltage, nonreversing magnetic starters and fusible disconnect switches in a common enclosure. Fractional sizes and ratings in accordance with IEC recommendations are not acceptable. Provide fused 3-pole load break disconnect switches with time delay, dual element fuses, external operating handle, and lock-off facility.
[DOCX File]SECTION 22 05 13
https://info.5y1.org/fused-disconnect-switch-sizes_1_b53add.html
Provide fused disconnect switches for combination starters with Class R type fuse rejection clips. If breakers are shown, provide breakers with a minimum of …
[DOCX File]Manual transfer switch (MTS), molded case type, guide spec ...
https://info.5y1.org/fused-disconnect-switch-sizes_1_c2f24e.html
Provide a fused disconnect for control power. Provide a ground bus, neutral disconnect link, and neutral-to-ground bonding jumper as required for service entrance equipment. Provide ground fault protection for use with solidly grounded wye electric services of more than 150 volts to ground where the service disconnect rating is 1000A or more.
[DOC File]Section 13030 - Special Purpose Rooms
https://info.5y1.org/fused-disconnect-switch-sizes_1_aa16ee.html
Accessories including isolation mountings and racks, expansion valve, interconnecting piping, piping insulation, solenoid valves, fused disconnect switch or circuit breaker, motor starter and all necessary equipment to achieve the specified performance for each room. All …
[DOC File]Rotary Disconnect Switches Proc Spec_194R-SR001A-en-p.doc
https://info.5y1.org/fused-disconnect-switch-sizes_1_bc2b01.html
The rotary disconnect switches shall be interoperable with standard electrical equipment. UL/CSA FUSIBLE DISCONNECT SWITCHES. RATINGS. The fusible rotary disconnect switches shall have UL/CSA ratings in 100, 200, 400, 600, and 800A sizes (at 600 VAC), with power/voltage as indicated on the drawings: 30 through 200 HP at 240V.
SECTION 262816.11 - SAFETY DISCONNECT SWITCHES
Switch assembly and operating handle shall be an integral part of the enclosure base. Switches rated 30 A to 600 A shall have reinforced fuse clips. Switch blades shall be readily visible in the “ON” and “OFF” position. Switch operating mechanism shall be non-teasable, positive quick-make/quick-break type.