Pressure tank for water heater
[DOC File]Lochinvar
https://info.5y1.org/pressure-tank-for-water-heater_1_c27acd.html
The water heater tank shall be constructed in accordance with ASME Boiler and Pressure Vessel Code requirements, stamped and registered with the National Board of Boiler and Pressure Vessel Inspectors. The tank shall have a 125 PSI working pressure. All tanks shall be glass lined with vitreous glass enamel and fired at 1600 F to ensure a ...
[DOC File]Commissioning - M&E Prefunctional Checklists
https://info.5y1.org/pressure-tank-for-water-heater_1_0294f9.html
Piping hydrostatic pressure test completed according to contract documents (report attached) No leaking apparent around fittings ASME pressure vessel data sheet or certification tag posted and inspection complete for each expansion tank and storage tank Expansion tanks verified to not be air bound and system completely full of water.
SECTION 15514 - DOMESTIC WATER HEATERS
The storage tank shall be ASME HLW stamped and National Board Registered for a maximum allowable working pressure of 150 psi and pressure tested at 1-1/2 times working pressure. On tanks 250 gallons and larger, tank design will include a manway access to the tank interior.
[DOCX File]Section 22 34 00 - FUEL-FIRED DOMESTIC WATER HEATERS
https://info.5y1.org/pressure-tank-for-water-heater_1_2c9f02.html
Before piping connections are made, the water heaters shall be tested at a hydrostatic pressure of 1380 kPa (200 psig) and 1654 kPa (240 psig) for a unit with a MAWP of 1104 kPa (160 psig). If any leakage is found on the water heater, the water heater shall be replaced with a …
[DOCX File]Prefuctional Checklist - DeCA Facilities
https://info.5y1.org/pressure-tank-for-water-heater_1_b792e0.html
Temperature sensors have been installed in the correct locations and connected to the RMCS as instructed by the domestic hot water system control diagram. 28 Thermostat furnished with the tank has been installed in the correct location on the supply line and is reporting back to the internal hot water heater control panel.
[DOC File]SECTION 15578 - PACKAGED HIGH PRESSURE STEAM …
https://info.5y1.org/pressure-tank-for-water-heater_1_64c84f.html
The tank must be constructed in accordance with Section VIII of the ASME Water heater and Pressure Vessel Code. D. HOT WATER STORAGE TANK The hot water storage tank shall be constructed of carbon steel and glass lined with a minimum of 10 mils of untonium glass suitable for temperatures up to …
SECTION 223000 - PLUMBING EQUIPMENT
Unit approved by AGA as automatic storage-tank water heater and [automatic circulating-tank water heater] [for] [operation at 180 F] [operation on combustible floors] [high-altitude installation]. Automatic water thermostat with temperature range adjustable from 120 to 180 F, gas pressure regulator, multi-ribbon or tubular burner, 100 percent ...
[DOC File]SECTION 235500 - FUEL-FIRED HEATERS
https://info.5y1.org/pressure-tank-for-water-heater_1_6aed65.html
After the water heater has been installed, the Subcontractor shall boil out the water heater and the entire piping system at low pressure for a period of not less than 8 hours by recirculating a solution consisting of 4 lb trisodium phosphate for each 1000 lb of water contained in the system.
[DOCX File]Section 22 33 00 - ELECTRIC DOMESTIC WATER HEATERS
https://info.5y1.org/pressure-tank-for-water-heater_1_af229f.html
Before piping connections are made, water heaters shall be tested with hydrostatic pressure of 1380 kPa (200 psig) and 1654 kPa (240 psig) for a unit with a MAWP of 1104 kPa (160 psig). Any domestic water heater leaking water shall be replaced with a new unit at no additional cost or time to the Government.
[DOC File]Specifications for Solar Water Heating Systems
https://info.5y1.org/pressure-tank-for-water-heater_1_7e2bef.html
Include with each system, components that consist of a solar collector array, array support structure, storage tank, interconnecting piping and fittings, tempering mixing valve, flush-and-fill valves, pressure relief valves,and as required by the system type, any necessary pumps, controls or heat exchangers, as well as all other accessories and ...