Nema disconnect ratings
[DOC File]Section 08360 - Overhead Doors
https://info.5y1.org/nema-disconnect-ratings_1_c86bb6.html
Disconnect Device: Provide hand-operated disconnect or mechanism for emergency manual operation while disconnecting motor, without affecting timing of limit switch. ... Provide control equipment complying with NEMA ICS1, NEMA ICS 2, and NEMA ICS 6, with NFPA 70 Class 2 control circuit, maximum 24-V, AC or DC. ... (0.2 m/s) and not more than 1 ...
[DOC File]Cooper Industries
https://info.5y1.org/nema-disconnect-ratings_1_591981.html
Voltage and ampacity ratings of the disconnect. Voltage, ampacity, and interrupting ratings of fuses. Branch device ratings including: Voltage, ampacity, and interrupting ratings of fused branch devices CLOSEOUT SUBMITTALS. Submit ten copies of: Final as-built drawings, assembly and component device ratings as required with Section 1.04
[DOC File]Section 26 29 21 - DISCONNECT SWITCHES
https://info.5y1.org/nema-disconnect-ratings_1_40fc1e.html
A. In accordance with UL 98, NEMA KS1, and NEC. B. Shall have NEMA classification General Duty (GD) for 240 V switches and NEMA classification Heavy Duty (HD) for 480 V switches. C. Shall be HP rated. D. Shall have the following features: 1. Switch mechanism shall be the quick-make, quick-break type. 2. Copper blades, visible in the OFF ...
[DOC File]PSG Section 16441A - Eaton
https://info.5y1.org/nema-disconnect-ratings_1_b92f43.html
30 A to 60 A NEMA 1 enclosures shall have tangential knockouts on the top, bottom and sides of the enclosure. NEMA 3R enclosures shall have tangential knockouts on the bottom and sides. (Not applicable to NEMA 1 plug-fuse type). HEAVY-DUTY SAFETY SWitCHES. Provide switches as shown on drawings, with the following ratings: 30 to 1200 amperes
SECTION 262816.11 - SAFETY DISCONNECT SWITCHES
NEMA 3R rainproof. NEMA 4X watertight corrosion-resistant . 30 A to 200 A – [304 stainless steel] [316 stainless steel] 400 A to 1200 A – [304 stainless steel] [316 stainless steel] NEMA 12 dust-tight and oil-tight special industry (dual NEMA 12/3R rating through 800 A). Factory installed ground terminal block. Paint color shall be ANSI 61 ...
[DOC File]Cooper Bussmann ® - Cooper Bussmann manufactures ...
https://info.5y1.org/nema-disconnect-ratings_1_92d081.html
b. Main disconnect terminations shall be rated for 75°C, Cu Only. J. NEMA 1 panelboards shall be field convertible for top or bottom incoming feed. NEMA 3R panelboards are bottom feed only. 2.04 MAIN DISCONNECT. A. Permanently installed lockout means shall be provided on the main disconnect for lockout tagout procedures.
[DOC File]ENERGY LABS, INC.
https://info.5y1.org/nema-disconnect-ratings_1_d1684c.html
A main input disconnect shall mount within the standard NEMA 1 or NEMA 12 enclosure for positive power disconnect of the VFD. It shall have the capability for door padlocking. A three phase 3% impedance input line reactor shall be provided to minimize drive harmonics on an A-C line and protect the drive from damaging electrical system transients.
[DOCX File]SECTION 22 05 13
https://info.5y1.org/nema-disconnect-ratings_1_b53add.html
Provide magnetic starters for three phase motors in accordance with the requirements listed in the Contract Documents. Motor starters shall be full voltage non-reversing "across the line" magnetic type, rated in accordance with NEMA standard sizes and horsepower ratings. Magnetic starters shall not be less than NEMA size one.
[DOC File]Visible Blade Disconnect Switches Procurement Specifications
https://info.5y1.org/nema-disconnect-ratings_1_63612e.html
The cable-operated disconnect switches shall have UL/CSA/NEMA or IEC ratings and 30, 60, 100, 200, 400 and 600A sizes, with power/voltage as indicated on the drawings. The cable-operated disconnect switches shall have (UL) IEC-rated insulation voltage, Ui, of (600) 660V.
[DOC File]PSG Section 26 28 16.13 - Eaton
https://info.5y1.org/nema-disconnect-ratings_1_b52be5.html
30 A to 60 A NEMA 1 enclosures shall have tangential knockouts on the top, bottom and sides of the enclosure. NEMA 3R enclosures shall have tangential knockouts on the bottom and sides. (Not applicable to NEMA 1 plug-fuse type). HEAVY-DUTY SAFETY SWitCHES. Provide switches as shown on drawings, with the following ratings: 30 to 1200 amperes
Nearby & related entries:
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Hot searches
- heart disease in cats treatment
- list of nyc doe principals
- what are some examples of social structure
- bank of america housing program
- university of pennsylvania finance depart
- treatment for heart ischemia
- percent of increase and decrease calculator
- newton s law of gravitation calculator
- mt land ownership map
- men who don t want marriage